Instruction manual integra motor minder owner manual dvd reglomat rt 20 manual krone baler manuals case 2470 service manual hasbara propaganda manual ascent delta v. Integra motor minder pump protector manufacturers integra motor minder pump protector suppliers Directory - Browse integra motor minder pump protector products,Choose.

That being said the option that we do have is using the NM-16SW switching module in a router which gives us some capabilities. Cisco ios router images download Now let’s see what “switching” options we have. You might have noticed that in the newer versions of GNS3 there’s a Etherswitch Router. Now you are probably wondering ‘which capabilities’ so let’s have a look what we can do. This is a Cisco 3725 with the NM-16SW module so only the icon is different.

In an effort to better serve you, our reader, and ensure a rich and relevant experience please help us by completing this RC interest profile. 1) Interest Level (check one) Browsing Interested Own A Vehicle 2) Vehicle Type (check any) All On-road Car Rally Car 2WD Buggy 4WD Buggy Scale or Trail Truck Stadium Truck Monster Truck Short-course Truck 3) Vehicle Size (check any) All Mini 1/12 1/10 1/8 1/5 4) Vehicle Fuel (check any) All Gas Nitro Electric 5) Skill Level (check one) Beginner Intermediate Advanced Pro 6) Your Email (confidential) 7) Your Name (confidential).

Integra Motor Minder

Mounting Wiring is done to unpluggable terminal strips on the rear of the unit. There are three ways to mount:. On door or raceway - use cutout template. Panel mount - use template + optional Bezel Kit (no charge). On wall - on standard outdoor junction box + optional Outlet Box Adapter (no charge) Voltage 120 volts AC is taken from two of the phases. If the motor starter already has a 120-volt control transformer with 10VA of free capacity, it can be used. Otherwise, install a separate transformer.

It is okay if the secondary is grounded. BE SURE TO NOTE WHICH TWO PHASES SUPPLY THE TRANSFORMER. In a 120/208V three-phase system, the 120V MUST come from a transformer connected to two of the phases. The 120V phase to ground voltage cannot be used.

Current The current signal is taken from the REMAINING phase. This current sample passes through the Range Finder Toroid. It is VERY IMPORTANT that the current signal comes from the phase that IS NOT supplying the 120V control transformer. Be extra careful when the machine has reversing starters or multi-speed windings. If a wrong phase is used, the control will either:. Work backwards. Have reduced sensitivity.

4-20 MILLIAMP ANALOG OUTPUT The Analog Output is directly proportional to Full Scale capacity. It is always active.

500 ohm maximum connected impedance. Terminal 2 - 4-20mA - Positive Terminal 3 - 4-20mA - Negative Use twisted pair or in noisy environments, use shielded cable. Ground shield at other end. Use the Full Scale capacity from the chart to scale external meter, chart recorders or computers.

THE PMP-25 POWERS THE 4-20MA SIGNAL DON'T USE AN EXTERNAL DC POWER SUPPLY. TO SET FULL SCALE. After hook-up, find your HP, KW or% from the chart. Decide if you want to display HP,% or KW.

The Scalecycles through the choices shown below and blinks slowly for each choice. Each press of Scalemoves you to the next choice FRONT PANEL SET-UP TIPS 1.None of the settings will be changed until you hold down and the fast blinking stops. 2.Five seconds after you have pressed a button, the control will return to normal operation. 3.If you hold down the digits will continue to change. 4.You only need to do when you install the PMP-25 (or if you change the hook-up). ADJUSTMENTS SET POINT - HIGH: The HIGH relay will switch when the load is above the HIGH. SET POINT - LOW: The LOW relay will switch when the load is below the LOW.

Start-up Timer The Start-up Timer bypasses the Control during motor startup to avoid false trips because of current inrush. For convenience, the TIMING BEGINS WHEN THE MOTOR STARTS. The Start-up LED stays lit until the start-up period is over.

The start-up time should be:. Long enough so that the load has stabilized.

Delay Timers To avoid nuisance trips from short overloads, Delay Timers bypass the Control for the selected time. The relays won't trip until the time is exceeded. If the trip condition goes away before the time is up, the timer resets to zero. Start with minimum Delay. If you are getting trips where you don't want them, increase the Delay Time. TO VIEW AND CHANGE THE SET POINTS AND DELAY TIMES cycles through the choices.

The LED for each choice will turn ON.To change a setting, use Press ENTER until quick blinking stops to store your new choice. After 5 seconds if you haven't pressed any buttons, control will return to normal operation. ADJUSTMENT TIPS FOR CENTRIFUGAL PUMPS From Pump Curves Use the recommended minimum and maximum flows and horsepower for your initial set points.

Instruction Manual Integra Motor Minder

Actual Operation Low Trip - Run the pump with the OUTLET valves closed. This is the minimum flow. Set the low trip about here. High Trip - Run the pump with all valves wide open. This is the maximum flow.

Set the high trip about here. Make adjustments if you get nuisance trips. V-Series Load Controls and UPC Power Cells are used together to protect equipment in Variable Speed motor drive applications. The UPC monitors motor power and sends a 0-10V signal to the V-Series Load Control. Each Load Control has adjustable set points and relay outputs.

The set point configuration differs depending on the application and is called out by a specific model number. The UPC measures True Power ( Watts ) on the output side of AC or DC motor drives and is field scaleable from small motors to 150 HP. Response time is field adjustable from 500 ms to 12 Sec. The UPC-FR has a fast Response time field adjustable from 50 ms to 1.2 Sec.

The V-Series Load Controls read the measured load on a digital display in either HP, KW or% Load. The meter also reads the set point and delay settings during setup. A HIGH trip set point will trip an output form C relay on an increase in load and a LOW trip set point will trip an output form C relay on a loss of load.

Reset can be done manually, remotely with a switch or automatically using jumpers on the resets. A 4-20ma analog output is also provided. PFR-1550V - Has one adjustable set point that can be programed for either HIGH trip or LOW trip.

PFR-1750V - Has two adjustable set points that are configured for HIGH trip. ROC-50V - Has two adjustable set points. One is configured for HIGH trip (Max. Limit) and the other is a RATE OF CHANGE set point that reacts to fast acting loads like jam conditions on conveyors, indexing equipment etc. Use with UPC-FR for Fast Response. PMP-25V - Has two adjustable set points configured for HIGH trip and LOW trip.

The Mounting Template ships with the V-series control and is used to mark hole punches for mounting on the outside of a panel door or raceway. To mount behind panel door or raceway use template to make a rectangular cut out and the BEZEL is used. Ask for the BEZEL kit when ordering ( no charge ). Gaskets are provided for both mounting options to maintain NEMA 4 integrity. The OUTLET BOX ADAPTER is used for a surface or backplane mount. This adapter will adapt to an OUTLET BOX so the V-Series connectors are spaced off the backplane of the panel.

Ask for OUTLET BOX ADAPTER when ordering (no charge). Gaskets are provided.